Welcome to Nanjing Kongying Fire Equipment Co., Ltd.!
暂时没有内容信息显示
Please add data record on website background.
>
Products

Products

列表

Superfine Dry Powder Fire Extinguishing System - Non Stored-pressure Suspended

Superfine Dry Powder Fire Extinguishing System - Non Stored-pressure Suspended

IntroductionSuspendedsuperfinedrypowderfireextinguishingsystemisdevelopedanddesignedforrelativelynarrowplacessuchasdistributionrooms,cabletunnels,communicationbasestations,computerlabs,ships,subway,andundergroundtunnels.Ithasthefollowingadvantages:Suspendedsuperfinedrypowderfireextinguishingsystemisdevelopedanddesignedforrelativelynarrowplacessuchasdistributionrooms,cabletunnels,communicationbasestations,computerlabs,ships,subway,andundergroundtunnels.Ithasthefollowingadvantages:2.Convenientinstallationanduse:Itiseasytoinstallonlythroughsuspendingovertheprotectedobject,becausethereisnoneedtopunchholesonthewallandinstallplentyofpipesandancillaryfacilities.3.Twostartingmodes,reliableperformanceA.Temperaturecontrolstartingbytemperature-sensingelement:Inthecaseoffire,theroomtemperatureexceedsthenominaloperatingtemperatureofnozzletemperature-sensingelement,glassballsexpandandbreakafterbeingheated,pressureplateonthenozzlewillbepulledoffbypressureinthepowdertank,thenfireextinguishingagentisejectedquicklyundertheactionofdrivinggastoextinguishfire.B.Electricalstarting:Inthecaseoffire,thefirealarmcontrolsystemdetectsfireandthenfirealarmcontrollerconfirmsitandsendoutfireextinguishinginstructionstothefireextinguishingcontrolpanel,thecontrolpaneloutputstheactionelectricsignaltoconnectfirepowersupplytotheelectronicstarteronthefireextinguishingsystem,thenglassballsexpandandbreakaftertemperature-sensingelementisheated,andthenozzleisopenedtoejectfireextinguishingagent. DetailedParameter SpecificationWorkingtemperatureWeightofagentWorkingpressureProtectioncapacityFZXA0.5-40~50℃0.5Kg-3m3FZXA2.0-40~50℃2Kg-12m3FZXA5.0-40~50℃5Kg-30m3

Superfine Dry Powder Fire Extinguishing System - Stored-pressure Suspended

Superfine Dry Powder Fire Extinguishing System - Stored-pressure Suspended

IntroductionSuspendedsuperfinedrypowderfireextinguishingsystemisdevelopedanddesignedforrelativelynarrowplacessuchasdistributionrooms,cabletunnels,communicationbasestations,computerlabs,ships,subway,andundergroundtunnels.Ithasthefollowingadvantages:1.Becausesuperfinedrypowdercansuspendintheairforacertaintimeduetosmallparticlesizeandgoodfluidity,itcanbeusedforself-extinguishmentinrelativelyclosedspacebytotalflooding,orforself-extinguishmentforpartialprotectionofopenplaces.2.Convenientinstallationanduse:Itiseasytoinstallonlythroughsuspendingovertheprotectedobject,becausethereisnoneedtopunchholesonthewallandinstallplentyofpipesandancillaryfacilities.3.Twostartingmodes,reliableperformanceA.Temperaturecontrolstartingbytemperature-sensingelement:Inthecaseoffire,theroomtemperatureexceedsthenominaloperatingtemperatureofnozzletemperature-sensingelement,glassballsexpandandbreakafterheated,pressureplateonthenozzlewillbepulledoffbypressureinthepowdertank,thenfireextinguishingagentisejectedquicklyundertheactionofdrivinggastoextinguishfire.B.Electricalstarting:Inthecaseoffire,thefirealarmcontrolsystemdetectsfire,firealarmcontrollerconformsittosendoutfireextinguishinginstructionstothefireextinguishingcontrolpanel,thecontrolpaneloutputstheactionelectricsignaltoconnectfirepowersupplytotheelectronicstarteronthefireextinguishingsystem,thenglassballsexpandandbreakaftertemperature-sensingelementisheated,andthenozzleisopenedtoejectfireextinguishingagent. DetailedParameter SpecificationWorkingtemperatureWeightofagentWorkingpressureProtectioncapacityFZXA4.0/1.2-20~50℃4Kg1.2MPa27m3FZXA8.0/1.2-20~50℃8Kg1.2MPa54m3

Page up
1
2