Superfine Dry Powder Fire Extinguishing System - Non Stored-pressure Suspended
IntroductionSuspendedsuperfinedrypowderfireextinguishingsystemisdevelopedanddesignedforrelativelynarrowplacessuchasdistributionrooms,cabletunnels,communicationbasestations,computerlabs,ships,subway,andundergroundtunnels.Ithasthefollowingadvantages:Suspendedsuperfinedrypowderfireextinguishingsystemisdevelopedanddesignedforrelativelynarrowplacessuchasdistributionrooms,cabletunnels,communicationbasestations,computerlabs,ships,subway,andundergroundtunnels.Ithasthefollowingadvantages:2.Convenientinstallationanduse:Itiseasytoinstallonlythroughsuspendingovertheprotectedobject,becausethereisnoneedtopunchholesonthewallandinstallplentyofpipesandancillaryfacilities.3.Twostartingmodes,reliableperformanceA.Temperaturecontrolstartingbytemperature-sensingelement:Inthecaseoffire,theroomtemperatureexceedsthenominaloperatingtemperatureofnozzletemperature-sensingelement,glassballsexpandandbreakafterbeingheated,pressureplateonthenozzlewillbepulledoffbypressureinthepowdertank,thenfireextinguishingagentisejectedquicklyundertheactionofdrivinggastoextinguishfire.B.Electricalstarting:Inthecaseoffire,thefirealarmcontrolsystemdetectsfireandthenfirealarmcontrollerconfirmsitandsendoutfireextinguishinginstructionstothefireextinguishingcontrolpanel,thecontrolpaneloutputstheactionelectricsignaltoconnectfirepowersupplytotheelectronicstarteronthefireextinguishingsystem,thenglassballsexpandandbreakaftertemperature-sensingelementisheated,andthenozzleisopenedtoejectfireextinguishingagent. DetailedParameter SpecificationWorkingtemperatureWeightofagentWorkingpressureProtectioncapacityFZXA0.5-40~50℃0.5Kg-3m3FZXA2.0-40~50℃2Kg-12m3FZXA5.0-40~50℃5Kg-30m3